Plan Review Notes
Plan Review Notes For Permit 01021178
Permit Number 01021178
Review Stop M
Sequence Number 5
Notes
Date Text
2001-11-19 00:00:00******************DENIED****************
  
  
 REVISED PLAN SHEETS M-203,204 & 205
 UNDER NOTES:4. (1) VENTILATION SHAFT
 NOT A FIRE RATED CHASE.AS PER 1997
 SMC 610.4, DUCTS EXTENDING THROUGH MORE
 THAN ONE FLOOR SHALL BE PROTECTED BY A
 SHAFT ENCLOSURE HAVE A FIRE RESISTANCE
 OF NOT LESS THAN 1 HOUR FOR BUIDLINGS
 LESS THAN FOUR STORIES IN HEIGHT (2 HR -
 FOR BUIDLINGS 4 STORIES AND MORE).
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.