| Plan Review Notes For Permit 01021178 |
| Permit Number |
01021178 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-07-12 00:00:00 | *******************PROVISO************** | | | | | | TYPE IV | | | | | | NOTHING ON PLANS HAVE CHANGED. | | | | | | PLEASE TAKE NOTE TO THE FOLLOWING ISSUES | | | | | | | | | 1.AS STATED IN REVIEW DATED 6/5/01, | | | PLAN M-106 DETAIL OF A/C CLOSET, | | | PROVIDE OVERFLOW PAN FOR UPPER | | | FLOORS ONLY....OVERFLOW PAN SHALL | | | GO ON EVERY FLOOR TO PREVENT DAMAGE | | | TO CARPET, WALLS AND INTERIOR OF | | | APARTMENT. | | | | | | 2.AS DISCUSSED IN MEETING WITH CARLOS | | | AT CITY HALL, AS PER AMENDED 1997 | | | SPC 804.3, #5. CONDENSATE DRAINS | | | SHALL VENT TO ATMOSPHERE, IT SHALL | | | NOT VENT INTO THE WALL AS SHOWN ON | | | THE DETAIL.SHOULD TERMINATION BE | | | IN THE ATTIC, IT SHALL BE A MINIMUM | | | OF 6" ABOVE THE INSULATION. | | | | | | PLEASE REMOVE/CORRECT NOTES THAT REFER | | | TO DETAILS ON PLANS THAT ARE NOT IN THE | | | PLAN SET OR ARE ON A DIFFERENT PLAN ALL | | | TOGETHER (EXAMPLE:SHAFT ENCLOSURE IS | | | SAID TO BE ON ARCHITECTURAL PLAN SHEET | | | A-13 #25). | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS 659-8096 EXT. 8388. |
|