2001-04-04 00:00:00TYPE II BUILDING
 BUILDING # 4,13 & 15
 PROJECT: 01021178
 ARCH. MOURIZ SALAZAR
 PHONE (305) 273-9911
 FAX)305)
 BUILDING 4TYPE II
  
 1)- SBC 1007.3.1: STAIR CALCULATION
 REQUIRES BETWEEN >24" &<25".
  
 2)- GENERAL STRUCTURAL NOTES S-4 (11)
 DESIGN LOADS,
 A)- DESIGN IS TO COMPLY WITH THE 1997
 STANDARD BUILDING CODE.
 B)- WIND LOAD CRITERIA, BASIC LOAD
 VELOCITY 110 MPH, ASCE 7-95.
  
 3)- FAIR HOUSING ACT CHAPTER 6.
 A)- LOCATION OF GRAB BARS FOR TUB IS
 32" MIN. & 38" MAXIMUM.
 B)- WATER CLOSET BACKING BEHIND THE
 WATER CLOSET WHEN THER IS NO WING
 WALL.SEE PAGES A-5.1,5.2,5.3, 5.6
 AND 5.10.
 C)_ A 5.6 MASTER BATH LAV DOES NOT MEET
 THE PARALLEL APPROACH AT THE LAV,
 30" X 48" ARE REQUIRED.
 D)- SHEET A-6: MAIL BOXES: FAIR HOUSING
 CHAPTER 2 REFERS TO FL ACCC CODE
 REACH & RANGES, SIDE APPROACH
 SECTION (4.2.6) MAX. HEIGTH 54"
 MIN. HEITH 0"-9".
 E)_ S-1.1, (4) C-1 APARTMENTS DEPICTS
 1/2" VERTICAL DROP + THRESHOLD, SEE
 FL ACC. CODE 4.13.8 THRESSHOLDS AT
 DOORWAYS, 2/1.
  
 4)- SHEET A-9 DETAIL #28: SOFFIT DETAIL
 DOESN'T GIVE THE ANCHORAGE TO THE STRUC-
 TURAL SLAB ABOVE.
  
 5)_ SHEET A 4.1 2ND FL UNIT C-1 DETAILS
 39/43, MISSING1 LAYER OF 1/2"DRYWALL.
  
 6)SH A4-5 NOTE 20, HI BIBBED LATH,
 SBC 2504.2.2 SEC ASTM C 1063.7.10.23
 3/8" RIB LATH ATTACHED TO HORIZONTAL
 WOOD SUPPORTS REQUIRES NAILS OR STAPLES
 TO PROVIDE 1 3/4" PENETRATION INTO
 HORIZONTAL WOOD SUPPORTS, 3/4" INTO
 VERTICAL SUPPORTS.
  
 7)- SHEET A 3.1 NOTE #12, CANVAS AWNINGS
 ON TUBULAR STEEL FRAMES REQUIRES A SEP-
 ERATE PERMIT, (PER BUILDING).
  