| Plan Review Notes For Permit 01021176 |
| Permit Number |
01021176 |
|
| Review Stop |
M |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2002-01-30 00:00:00 | *******************DENIED*************** | | | | | | | | | PLAN SHEET M-302 THROUGH M-305 NOTES: | | | #4- 1,"VENTILATION SHAFT (NOT A FIRE | | | RATED CHASE)". | | | | | | DUCTS PENETRATING MORE THAN 1 FLOOR | | | SHALL BE PROTECTED BY A SHAFT ENCLOSURE | | | AS PER 1997 SMC 610.4 & NFPA 90A | | | 3-3.4.1.1 HOUR RATING IS REQUIRED FOR | | | BUILDINGS LESS THAN 4 STORIES AND 2 | | | HOUR RATING FOR BUILDINGS 4 STORIES AND | | | MORE IN HEIGHT. | | | | | | | | | THE ABOVE ISSUED WAS DISCUSSED IN A | | | MEETING ON JANUARY 18,2002.PLEASE SEE | | | ATTACHED LETTER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|