| Plan Review Notes For Permit 01021176 |
| Permit Number |
01021176 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-11-21 00:00:00 | REVISION DENIED | | | REFERENCE: SPC-94 - FHA AMEND 98 DESIGN | | | MANUAL | | | | | | 1) REVISION PAGES DO NOT MATCH PAGE NUM- | | | BERS IN MASTER SET REVIEW FOR PERMIT. | | | 2) ALL REVISIONS SHALL BE DATED AND IN- | | | DICATED WITH EITHER A CLOUD, DART, OR | | | TRIANGLE FOR REVIEW. | | | 3) PAGE SUBMITTED P-3.1 PIPE SIZE FOR | | | BLDG DRAIN NOT APPROVED. ONLY 180 FU | | | ALLOWED ON 4" PIPE AT 1/8" PER FOOT. | | | 4) PLEASE RESUBMIT REVISION WITH MATCH- | | | ING PAGE NUMBERS AND SHOW WHAT IS BEING | | | REVISED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|