Plan Review Notes
Plan Review Notes For Permit 01021176
Permit Number 01021176
Review Stop P
Sequence Number 4
Notes
Date Text
2001-11-21 00:00:00REVISION DENIED
 REFERENCE: SPC-94 - FHA AMEND 98 DESIGN
 MANUAL
  
 1) REVISION PAGES DO NOT MATCH PAGE NUM-
 BERS IN MASTER SET REVIEW FOR PERMIT.
 2) ALL REVISIONS SHALL BE DATED AND IN-
 DICATED WITH EITHER A CLOUD, DART, OR
 TRIANGLE FOR REVIEW.
 3) PAGE SUBMITTED P-3.1 PIPE SIZE FOR
 BLDG DRAIN NOT APPROVED. ONLY 180 FU
 ALLOWED ON 4" PIPE AT 1/8" PER FOOT.
 4) PLEASE RESUBMIT REVISION WITH MATCH-
 ING PAGE NUMBERS AND SHOW WHAT IS BEING
 REVISED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377