| Plan Review Notes For Permit 01021176 |
| Permit Number |
01021176 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-07-23 00:00:00 | ******************PROVISO*************** | | | | | | THE FOLLOWING ISSUES WHERE NOT ADDRESSED | | | FROM THE PREVIOUS REVIEW.PLEASE SUBMI | | | T REVISED DRAWINGS PRIOR TO FIRST INSPEC | | | TION. | | | | | | 1.AHU #2 NEEDS A RETURN AIR IN THE | | | "FUN CENTER". | | | | | | 2.AHU #1 NEEDS A RETURN AIR FROM THE | | | "CLUBROOM" AND THE "RECEPTION AREA". | | | | | | 3.PLAN NUMBER M-2.C, A/C CLOSET DETAIL | | | INDICATES VENT FROM CONDENSATE LINE | | | IS IN THE WALL.CONDENSATE SHALL | | | VENT TO THE ATMOSHPERE, AS PER | | | AMENDED 1994 SPC 804.3, #5.SHOULD | | | VENT TERMINATE IN THE ATTIC, IT | | | SHALL BE A MINIMUM OF 6" ABOVE THE | | | INSULATION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|