2001-07-23 00:00:00******************PROVISO***************
  
 THE FOLLOWING ISSUES WHERE NOT ADDRESSED
 FROM THE PREVIOUS REVIEW.PLEASE SUBMI
 T REVISED DRAWINGS PRIOR TO FIRST INSPEC
 TION.
  
 1.AHU #2 NEEDS A RETURN AIR IN THE
 "FUN CENTER".
  
 2.AHU #1 NEEDS A RETURN AIR FROM THE
 "CLUBROOM" AND THE "RECEPTION AREA".
  
 3.PLAN NUMBER M-2.C, A/C CLOSET DETAIL
 INDICATES VENT FROM CONDENSATE LINE
 IS IN THE WALL.CONDENSATE SHALL
 VENT TO THE ATMOSHPERE, AS PER
 AMENDED 1994 SPC 804.3, #5.SHOULD
 VENT TERMINATE IN THE ATTIC, IT
 SHALL BE A MINIMUM OF 6" ABOVE THE
 INSULATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.