| Plan Review Notes For Permit 01021175 |
| Permit Number |
01021175 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2001-11-19 00:00:00 | *******************DENIED*************** | | | | | | | | | REVISION FOR PLAN SHEET M-103,104 & | | | 105, INDICATE A REVISION (TRIANGLE) | | | DATED 5/7/01.THIS WAS NOT A REVISION | | | AND WAS NOT WITH THE PLANS APPROVED FOR | | | PERMIT.DUCTS PENETRATING MORE THAN 1 | | | FLOOR SHALL BE PROTECTED BY A SHAFT | | | ENCLOSURE AS PER 1997 SMC 610.4.1 HR | | | FIRE RATING UP TO 3 STORIES, 2 HR RATING | | | 4 STORIES OR MORE. | | | | | | PLEASE INDICATE ALL CHANGES BY CLOUDS | | | AND TRIANGLES ALONG WITH THE DATE OF | | | THE REVISION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|