Plan Review Notes
Plan Review Notes For Permit 01021175
Permit Number 01021175
Review Stop M
Sequence Number 3
Notes
Date Text
2001-07-11 00:00:00*******************PROVISO**************
 ALL TYPE I
  
 NOTHING ON PLANS HAVE CHANGED.
  
 PLEASE TAKE NOTE TO THE FOLLOWING ISSUES
  
  
 1.AS STATED IN REVIEW DATED 6/5/01,
 PLAN M-106 DETAIL OF A/C CLOSET,
 PROVIDE OVERFLOW PAN FOR UPPER
 FLOORS ONLY....OVERFLOW PAN SHALL
 GO ON EVERY FLOOR TO PREVENT DAMAGE
 TO CARPET, WALLS AND INTERIOR OF
 APARTMENT.
  
 2.AS DISCUSSED IN MEETING WITH CARLOS
 AT CITY HALL, AS PER AMENDED 1997
 SPC 804.3, #5. CONDENSATE DRAINS
 SHALL VENT TO ATMOSHPERE, IT SHALL
 NOT VENT INTO THE WALL AS SHOWN ON
 THE DETAIL.SHOULD TERMINATION BE
 IN THE ATTIC, IT SHALL BE A MINIMUM
 OF 6" ABOVE THE INSULATION.
  
 PLEASE REMOVE /CORRECT NOTES THAT REFER
 TO DETAILS ON PLANS THAT ARE NOT IN THE
 PLAN SET OR HAVE BEEN SHOWN ON
 DIFFIERENT PLAN (EXAMPLE:SHAFT
 ENCLOSURE IS SAID TO BE ON ARCHITECTURAL
 PLAN SHEET A-13 #25).
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS 659-8096 EXT. 8388.