Plan Review Notes
Plan Review Notes For Permit 01021175
Permit Number 01021175
Review Stop B
Sequence Number 2
Notes
Date Text
2001-06-12 00:00:00TYPE I BUILDING
 BUILDINGS: 1,3,5,8,10& 12
 PLAN CHECK: 01021175
 ARCH: MOURIZ SALAZAR
 PHONE : (305) 273-9911
 FAX ;(305) 273-
  
 BUILDING 1 TYPE I
  
 1)- SEE A5.6 MASTER BATH LAV DOESN'T
 MEET THE PARALLEL APPROACH AT LAV 30"X48
  
 2)- SEE A-6 MAIL BOX, FAIR HOUSING CHAP-
 TER 2 2.12 #9 REFERS BACK TO FL. ACC.
 ALLOWABLE REACH RANGES, SIDE MAX 54",
 MINIMUM 0'-9"
  
 3)- SH. A4-5 NOTE 20 HI RIB LATH SBC
 25042504.2.2 SEC ASTM C 1063.7.10.23
 3/8" RIB LATH ATTACHED TO HORIZONTAL
 WOOD SUPPORTS REQUIRES NAILS/ STAPLES TO
 PROVIDE 1 3/4" PENETRATION INTO HORIZONT
 AL WOOD SUPORTS, 3/4" INTO VERTICAL
 SUPPORTS, NAILED AT EVERY RIB.
  
 4)- SEE SECTION "D" SHEET A4.5 THE BOTTO
 M OF THE FOUNDATION HAS TO BE A MINIMUM
 OF 12" BELOW GRADE, SBC 1804.1.3.
  
 5)- ALL GENERAL NOTES LISTED UNDER THE
 CLUBHOUSEPERTAIN TO COMPONENTS & CLAD-
 DING DETAILS, ATTACHMENTS OF DOOR & WIN-
 DOW BUCKS, PRODUCT APPROVALS FOR GLAZED
 OPENINGS, SEE WEST PALM BEACH POLICY FOR
 LARGE MISSLE IMPACT RESISTANCE FOR LARGE
 PROJECTS.PRODUCT APPROVAL FOR OVERHEAD
 DOORS, AS WELL AS FOR ROOFING MATERIALS.
 THE CITY ACCEPTS SBCCI & DADE COUNTY PRO
 DUCT APPROVAL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412