Plan Review Notes
Plan Review Notes For Permit 01021175
Permit Number 01021175
Review Stop P
Sequence Number 1
Notes
Date Text
2001-07-14 00:00:00DENIED;
  
 1.BUILDING TYPE I, II, III, AND IV SHALL
 COMPLY WITH 94 SPC SEC. 710.2.4,
 CLEANOUTS; SHOW ALL CLEANOUT LOCATIONS
 ON PLANS.
  
 2.PAGE 105 PIPE SIZING FOR SANITARY
 PIPING IS NOT TO CODE. SEE TABLE 714.1
 NOTE 3.
  
 3.PAGE P105 AND P106 CONDENSATE PIPING
 SHALL NOT BE VENTED IN A/H CLOSET IF
 CLOSET IS A PLENUM. VENTS SHALL BE
 ABOVE THE CEILING.
  
 4.BACKFLOW PREVENTERS REQUIRED ON EACH
 BUILDING DOMESTIC WATER SUPPLY. NOT
 ADDRESSED ON TYPE II BUILDING. NOTE
 SHOULD BE NEXT TO SYMBOL DENOTING
 SIZE AND TYPE.
  
 5.PAGE P102 VENTS THRU ROOF ARE NOT
 PERMITED TO PENETRATE THE FIRE RATED
 ROOF ASSEMBLY 97 SBC 704.4.2.
  
  
 6.PAGE P-105 WATER RISER DIAGRAM. AIR
 CHAMBERS. REFUR TO 94 SPC 607.8.2 AND
 607.8.3 HAMMER ARRESTORS SHALL BE
 INSTALLED PER MANUFACTORS
 RECOMENDATIONS.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369