| 2001-07-14 00:00:00 | DENIED; | | | | | | 1.BUILDING TYPE I, II, III, AND IV SHALL | | | COMPLY WITH 94 SPC SEC. 710.2.4, | | | CLEANOUTS; SHOW ALL CLEANOUT LOCATIONS | | | ON PLANS. | | | | | | 2.PAGE 105 PIPE SIZING FOR SANITARY | | | PIPING IS NOT TO CODE. SEE TABLE 714.1 | | | NOTE 3. | | | | | | 3.PAGE P105 AND P106 CONDENSATE PIPING | | | SHALL NOT BE VENTED IN A/H CLOSET IF | | | CLOSET IS A PLENUM. VENTS SHALL BE | | | ABOVE THE CEILING. | | | | | | 4.BACKFLOW PREVENTERS REQUIRED ON EACH | | | BUILDING DOMESTIC WATER SUPPLY. NOT | | | ADDRESSED ON TYPE II BUILDING. NOTE | | | SHOULD BE NEXT TO SYMBOL DENOTING | | | SIZE AND TYPE. | | | | | | 5.PAGE P102 VENTS THRU ROOF ARE NOT | | | PERMITED TO PENETRATE THE FIRE RATED | | | ROOF ASSEMBLY 97 SBC 704.4.2. | | | | | | | | | 6.PAGE P-105 WATER RISER DIAGRAM. AIR | | | CHAMBERS. REFUR TO 94 SPC 607.8.2 AND | | | 607.8.3 HAMMER ARRESTORS SHALL BE | | | INSTALLED PER MANUFACTORS | | | RECOMENDATIONS. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|