Plan Review Notes
Plan Review Notes For Permit 01021175
Permit Number 01021175
Review Stop M
Sequence Number 1
Notes
Date Text
2001-04-06 00:00:00******************DENIED****************
  
  
 1.DRAWING NUMBER M-104 IN THE NOTES,
 "1 HOUR FIRE RATED SHAFT ENCLOSURE,
 SEE ARCHITECTURAL PLAN SHEET A-13
 DEATIL #25".NO SUCH DRAWING IN
 THIS SET OF PLANS.
  
 2.PLEASE INDICATE WHERE RETURN AIR
 IS LOCATED IN EACH APARTMENT.
  
 3.PLEASE PROVIDE DETAIL OF DRYER VENT
 TERMINATING IN THE SHAFT AND RISER
 TO THE ROOF.
  
 4.PLEASE PROVIDE DETAILS ON KITCHEN
 HOOD.
  
 5.IN "GENERAL HEATING, VENTILATION &
 AIR CONDITIONING NOTES", #13 F.,
 SHOULD READ "NON-COMBUSTIBLE"
 MATERIAL IS TO BE PROVIDED IN
 PLENUM SIDE.