Plan Review Notes
Plan Review Notes For Permit 01021175
Permit Number 01021175
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-08-02 00:00:001) WATER SUPPLY FOR FIRE HYDRANTS
 DURING CONSTRUCTION NEEDS TO BE
 RESOLVED. A WATER MAIN EXTENSION IS
 NEEDED AND THE DEVELOPER HAS SUGGESTED
 ALTERNATIVE SOLUTIONS FOR THIS ISSUE.
 2) NOTE ON PAGE A-1.2. INDICATES
 BUILDING WILL NOT BE FIRE SPRINKLER
 PROTECTED. THIS IS NOT CORRECT.
 3) STORAGE NOT PERMITTED UNDERNEATH
 STAIRS. STORAGE AREAS TO BE RATED AT
 LEAST THAT OF STAIRS.
 4) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 5) HOW IS THE DRYER EXHAUST RISER
 CLEANED OF COMBUSTIBLE LINT.
 6) HOW IS THE OUTER STAIRS BEING
 ILLUMINATED IN CASE OF POWER OUTAGE.
 7) FIRE ALARM RISER DIAGRAM SHOWS E.O.L.
 ONLY CLASS A OR FULLY ADDRESSABLE WILL
 PER PERMITTED.
 8) PROVIDE MORE DETAILS ON EGRESS
 WINDOWS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910