| Plan Review Notes For Permit 01021175 |
| Permit Number |
01021175 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-02 00:00:00 | 1) WATER SUPPLY FOR FIRE HYDRANTS | | | DURING CONSTRUCTION NEEDS TO BE | | | RESOLVED. A WATER MAIN EXTENSION IS | | | NEEDED AND THE DEVELOPER HAS SUGGESTED | | | ALTERNATIVE SOLUTIONS FOR THIS ISSUE. | | | 2) NOTE ON PAGE A-1.2. INDICATES | | | BUILDING WILL NOT BE FIRE SPRINKLER | | | PROTECTED. THIS IS NOT CORRECT. | | | 3) STORAGE NOT PERMITTED UNDERNEATH | | | STAIRS. STORAGE AREAS TO BE RATED AT | | | LEAST THAT OF STAIRS. | | | 4) BUILDING ADDRESS REQUIRED PER CITY | | | CODE 3343-00. | | | 5) HOW IS THE DRYER EXHAUST RISER | | | CLEANED OF COMBUSTIBLE LINT. | | | 6) HOW IS THE OUTER STAIRS BEING | | | ILLUMINATED IN CASE OF POWER OUTAGE. | | | 7) FIRE ALARM RISER DIAGRAM SHOWS E.O.L. | | | ONLY CLASS A OR FULLY ADDRESSABLE WILL | | | PER PERMITTED. | | | 8) PROVIDE MORE DETAILS ON EGRESS | | | WINDOWS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|