Plan Review Notes
Plan Review Notes For Permit 01021175
Permit Number 01021175
Review Stop B
Sequence Number 1
Notes
Date Text
2001-04-04 00:00:00TYPE I BUILDING
 BUILDINGS: 1,3,5,8,10 & 12
 PROJECT: 01021175
 ARCH. MOURIZ SALAZAR
 PHONE (305) 273-9911
 FAX(305)
 BUILDING 1TYPE I
  
 1)- SBC 1007.3.1: STAIR CALCULATION
 REQUIRES 2R+1T= >24",< 25"
  
 2)- GENERAL STRUCTURAL NOTES S-4 (11)
 DESIGN LOADS,
 A)- DESIGN IS TO COMPLY WITH THE
 1997 STANDARD BUILDING CODE.
 B)- WIND LOAD CRITERIA, BASIC LOAD
 VELOCITY 110 MPH ASCE 7-95.
  
 3)- FAIR HOUSING ACT: CHAP 6
 A)- LOCATION OF GRAB BAR AT TUB 32" MIN
 38" MAXIMUM.
 B)- WATER CLOSET BACKING BEHIND THE
 WATER CLOSET.
 SEE PAGES A-5.1,5.2, 5.3,5.6 & 5.10
 C)- A5.6 MASTER BATH LAV DOESN'T MEET
 THE PARALLEL APPROACH AT LAV, 30"
 X 48" CLEAR.
 D)- A-6: MAIL BOX, FAIR HOUSING CHAP.2
 REFER TO FL ACC REACH & RANGES,
 SIDE APPROACH (4.2.6) MAX HEIGTH54"
 MIN HEIGTH 0'-9".
 E)- S-1.1: (4) C-1 APTS DEPICTS 1/2
 VERTIAL DROP + THRESHOLD, SEE FL
 ACC CODE 4.13.8 THRESHOLDS AT DOOR-
 WAYS, 2/1.
  
 4)- SHEET A-9 DETAIL # 28: SOFFIT DETAIL
 DOESN,T GIVE ANORAGEOF SOFFIT TO THE
 5 1/2" STRUCTURAL SLAB.
  
 5)- SHEET A 4.1 2ND FL UNIT C-1 DETAILS
 39/43 ONE HR. KNEE WALL, SEE DETAIL ON
 A-10 DETAIL 43, MISSING 1 LAYER OF 1/2"
 DRYWALL.
  
 6)- SH. A4-5 NOTE 20, HI RIBBED LATH,
 SBC 2504..2.2 SEC ASTM C 1063.7.10.23)
 3/8" RIB LATH ATTACHED TO HORIZONTAL
 WOOD SUPPORTS REQUIRES NAILS/ STAPLES
 TO PROVIDE 1 3/4" PENETRATION INTO
 HORIZONTAL WOOD SUPPORTS, 3/4" INTO
 VERTICAL SUPPORTS.
  
 7)- SHEET A3.1 NOTE #12, CANVAS AWNINGS
 ON TUBULAR STEEL FRAMES REQUIRES A SEP-
 ERATE PERMIT, (PER BUILDING).
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 (8412)