Plan Review Notes
Plan Review Notes For Permit 01021160
Permit Number 01021160
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-03-02 00:00:001) PLEASE PROVIDE A DRAWING OF THE
 FIREFIGHTERS OVERRIDE PANEL. THE PANEL
 SHOULD PROVIDE A DEPICTION OF THE
 ATRIUM AND ASSOCIATED SMOKE EXHAUST
 EQUIPMENT.
 2) THE ATRIUM SMOKE EXHAUST SYSTEM
 SHALL BE ACTIVATED BY APPROVED SMOKE
 DETECTORS AT THE TOP OF ATRIUM, ADJACENT
 TO EACH RETURN AIR INTAKE FROM THE
 ATRIUM, THE REQUIRED FIRE SPRINKLER
 SYSTEM, THE REQUIRED FIRE ALARM SYSTEM,
 AND THE FIREFIGHTER OVERRIDE PANEL.
 RE: NFPA 101, THE LIFE SAFETY CODE, 1985
 EDTION, SECTION 6-2.2.3.5 (G)
 3) PLEASE PROVIDE TESTING EQUIPMENT THAT
 WILL BE USED TO TEST THE ATRIUM SMOKE
 EXHUAST SYSTEM. ALSO WILL SMOKE BOMBS
 OR SMOKE MACHINES BE USED TO TEST THE
 ATRIUM.
 4) PLEASE PROVIDE TETSING CRITERIA FOR
 THE ATRIUM.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved