| Plan Review Notes For Permit 01021160 |
| Permit Number |
01021160 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-03-02 00:00:00 | 1) PLEASE PROVIDE A DRAWING OF THE | | | FIREFIGHTERS OVERRIDE PANEL. THE PANEL | | | SHOULD PROVIDE A DEPICTION OF THE | | | ATRIUM AND ASSOCIATED SMOKE EXHAUST | | | EQUIPMENT. | | | 2) THE ATRIUM SMOKE EXHAUST SYSTEM | | | SHALL BE ACTIVATED BY APPROVED SMOKE | | | DETECTORS AT THE TOP OF ATRIUM, ADJACENT | | | TO EACH RETURN AIR INTAKE FROM THE | | | ATRIUM, THE REQUIRED FIRE SPRINKLER | | | SYSTEM, THE REQUIRED FIRE ALARM SYSTEM, | | | AND THE FIREFIGHTER OVERRIDE PANEL. | | | RE: NFPA 101, THE LIFE SAFETY CODE, 1985 | | | EDTION, SECTION 6-2.2.3.5 (G) | | | 3) PLEASE PROVIDE TESTING EQUIPMENT THAT | | | WILL BE USED TO TEST THE ATRIUM SMOKE | | | EXHUAST SYSTEM. ALSO WILL SMOKE BOMBS | | | OR SMOKE MACHINES BE USED TO TEST THE | | | ATRIUM. | | | 4) PLEASE PROVIDE TETSING CRITERIA FOR | | | THE ATRIUM. |
|