| Plan Review Notes For Permit 01021042 |
| Permit Number |
01021042 |
|
| Review Stop |
FS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-02-27 00:00:00 | 1) ENTIRE BUILDING IS TO BE COMPLETELY | | | FIRE SPRINKLER PROTECTED. THIS INCLUDES | | | ALL ELECTRICAL, MECHANICAL AND SERVICE | | | ROOMS. ALSO ALL VERTICAL SHAFTS ARE | | | TO PROTECTED WITH SPRINKLERS. | | | 2) ALL FIRE STANDPIPES ARE TO BE | | | EQUIPPED WITH 2 1/2 TO 1 1/2 REDUCERS. | | | 3) STANDPIPE SYSTEM TO PROVIDE 65 PSI | | | AT THE ROOF WHILE FLOWING WATER VIA | | | THE STANDPIPES. | | | 4) NO CUT SHEETS PROVIDED ON FIRE | | | SPRINKLERS, PIPING AND VALVES PLANNED | | | FOR USE. PLEASE PROVIDE THESE ITEMS | | | ON NEXT SUBMISSION. | | | 5) PLEASE PROVIDE MORE DETAILS ON FIRE | | | PUMP AND EMERGENCY GENERATOR. MORE | | | DETAILS ARE NEEDED ON THE FIRE PUMP | | | CONTROLLER AND APPURTENANT EQUIPMENT. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|