Plan Review Notes
Plan Review Notes For Permit 01021042
Permit Number 01021042
Review Stop FS
Sequence Number 1
Notes
Date Text
2001-02-27 00:00:001) ENTIRE BUILDING IS TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THIS INCLUDES
 ALL ELECTRICAL, MECHANICAL AND SERVICE
 ROOMS. ALSO ALL VERTICAL SHAFTS ARE
 TO PROTECTED WITH SPRINKLERS.
 2) ALL FIRE STANDPIPES ARE TO BE
 EQUIPPED WITH 2 1/2 TO 1 1/2 REDUCERS.
 3) STANDPIPE SYSTEM TO PROVIDE 65 PSI
 AT THE ROOF WHILE FLOWING WATER VIA
 THE STANDPIPES.
 4) NO CUT SHEETS PROVIDED ON FIRE
 SPRINKLERS, PIPING AND VALVES PLANNED
 FOR USE. PLEASE PROVIDE THESE ITEMS
 ON NEXT SUBMISSION.
 5) PLEASE PROVIDE MORE DETAILS ON FIRE
 PUMP AND EMERGENCY GENERATOR. MORE
 DETAILS ARE NEEDED ON THE FIRE PUMP
 CONTROLLER AND APPURTENANT EQUIPMENT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910