| 2002-07-08 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - FACBC-97 - SGC-97 |
| | |
| | 1) SHT P4.2 3" PLANTER DRAIN SHOWN ON |
| | FLAT DRAWING P1.0 MISSING FROM STORM |
| | RISER DIAGRAM. |
| | 2) SHT P1.2A REVISION SHOWS NO PIPING TO |
| | ROOF DRAINS, 1 NEW 4" RD-A, 2" SCUPPER |
| | DRAINS COL. LINE X15, 3" & 4" SCUPPER |
| | DRAINS COL. LINE BELOW X26. PLEASE |
| | CLAIRFY. ARE ORIGINAL ROOF DRAINS STILL |
| | BEING USED? ARE SCUPPERS SECONDARY |
| | DRAINS? IF SO THEY CAN NOT TIE INTO |
| | PRIMARY DRAIN SYSTEM. NO SECONDARY DRAIN |
| | SHOWN FOR LOWER ROOF TO THE LEFT SIDE. |
| | 3) PLEASE INDICATE WHERE ALL SECONDARY |
| | ROOF DRAINS DRAIN TO. |
| | 4) SHT P4.1 GREASE INTERCEPTOR DETAIL, |
| | 2 WAY CLEAN OUTS ARE REQUIRED FOR INLET |
| | & OUTLET SIDES OF GREASE INTERCEPTOR. |
| | 5) SHT P4.2 RAINWATER RISER DIAGRAM, THE |
| | AREA IN QUESTION ON COMMENT #2, (SHT P1. |
| | 2), IS NOT SHOWN ON RAINWATER RISER DIA- |
| | GRAM. PLEASE INDICATE WHERE THIS IS LO- |
| | CATED ON RISER DIAGRAM. |
| | 6) SHT P4.4 FUNNEL FLOOR DRAINS ARE NOT |
| | APPROVED. ALL INDIRECT WASTE SHALL DRAIN |
| | INTO A FLOOR SINK. PLEASE DELETE AND |
| | SHOW FLOOR SINKS. |
| | 7) SHT P4.5 SANT RISER DIAGRAM. PLEASE |
| | SHOW FIXTURE UNITS DRAINING IN SYSTEM. |
| | SHOW TOTAL AMOUNT AND SHOW DFU'S AS THEY |
| | ACCUMULATE IN SYSTEM. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |