| Plan Review Notes For Permit 01021024 |
| Permit Number |
01021024 |
|
| Review Stop |
FIRE |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2001-09-12 00:00:00 | 1) SECURITY FEAUTURES WHEN INSTALLED | | | ARE TO MEET THE REQUIREMENTS OF | | | " SPECIAL LOCKING ARRANGEMENTS" PER | | | THE LIFE SAFETY CODE, 1985 EDITION, | | | SECTION 5-2.1.6. THIS CODE REQUIRES | | | THE UNLOCKING OF DOORS "UPON ACTUATION | | | OF AN APPROVED SUPERVISED AUTOMATIC | | | FIRE DETECTION SYSTEM OR APPROVED | | | SUPERVISED AUTOMATIC FIRE SPRINKLER | | | SYSTEM | | | UNLOCK UPON LOSS OF POWER CONTROLLING | | | THE LOCK OR LOCKING MECHANISM AND | | | INITIATE AN IRREVERSIBLE PROCESS WHICH | | | WILL RELEASE THE LOCK WITHIN 15 | | | SECONDS WHENEVER A FORCE OF NOT MORE | | | THAN 15 LBS. IS CONTINOUSLY APPLIED. | | | OPERATION OF THE DOOR SHALL ACTIVATE A | | | SIGNAL IN THE VICINITY OF THE DOOR". | | | ALSO A "SIGN SHALL BE PROVIDED ON THE | | | DOOR ADJACENT TO THE RELEASE DEVICE | | | WHICH READS PUSH UNTIL ALARM SOUNDS. | | | DOOR CAN BE OPENED IN 15 SECONDS". | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|