| 2001-08-08 00:00:00 | ******************PROVISO*************** | | | | | | | | | REVISIONS FOR "CHILLER ROOM" WERE NOT A | | | PART OF THIS REVIEW.ALL CHILLER ROOM | | | REVISIONS NEED TO BE SUBMITTED WITH | | | PERMIT NUMBER 01040393. | | | | | | NOTE:CONDENSATE SHALL BE INDICATED ON | | | PLANS AND SHALL COMPLY WITH THE | | | AMENDED 1994 SPC 804.3.RTU 1 | | | ON PLAN SHEET H1.2A,SHALL NOT | | | "SPILL ON ROOF".FAN COIL UNITS | | | SHALL NOT GO INTO "SANITARY | | | PIPING".PLEASE SUBMIT | | | CONDENSATE FOR REVIEW. | | | | | | **** CONDENSATE NEEDS TO BE ADDRESSED | | | PRIOR TO MECHANICAL PERMIT BEING | | | ISSUED. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|