| 2001-06-04 00:00:00 | PLUMBING PLAN REVIEWDENIED |
| | (1) PREVIOUS COMMENTS NOT ADDRESSED |
| | SHT A1.1, A1.8,DOOR SWINGS INTO CLEAR |
| | FLR SPACE OF LAV, RM # 305,SEC 4.17.5 |
| | (2) SHT P1.0,P4.1 GREASE TRAP SIZE AND |
| | TYPE TO BE REVIEWED BY WPB,RSTP ENVIRO- |
| | MENTAL COMPLIANCE RODNEY COMPO 561-837- |
| | 4074.WITH CUT SHTS FROM MFG. |
| | (3) SHT A6.13 ELEVATIONS,DIMENSIONS OF |
| | H/C PLUMBING FIXTURES INCLUDING URINALS, |
| | (4) SHT P1.1B CHILLER PLANT,REST RM #132 |
| | SHOWER COMPARTMENT,TO COMPLY W/FACBC 97 |
| | SEC 4.21, FIG. 35 A OR B. |
| | (5) SHT P3.1 PROVIDE A LIST OF KITCHEN |
| | EQUIPMENT FOR PLUMBING,GAS FIXTURES, |
| | SPC 94 SEC 104.3 |
| | (6) SHT P4.1 DISHWASHER TO BY PASS G/W, |
| | CONNECT TO SANITARY SEWER, LOCAL ORD. |
| | #2938-96 WPB,RSTP. |
| | (7) SHT P4.1 PROVIDE A COMPLETE GAS |
| | ISOMETRIC,FROM THE METER TO THE FARTHEST |
| | POINT OF USE,INCLUDE BOILER & KITCHEN. |
| | SEE ATTACHED GAS PERMIT APPLICATION REQ- |
| | UIRMENTS,SGC 97 SEC 104.3 ADDRESS EACH |
| | OF NINE ITEMS. |
| | (8) SHT P4.2 SHOW CALCULATIONS FOR ROOF |
| | & SCUPPER DRAINS, INCLUDING VERTICAL |
| | WALLS,ALSO SECONDARY DRAINS FROM ABOVE |
| | DRAINING ON TO LOWER ROOFS.SPC 94 |
| | SEC 1101.2,1108.3,1109.1 |
| | (9) SHTP4.1 SPC 94 SEC 921.4 GEN. DESIGN |
| | HORIZONTAL WASTE & VENT SYSTEM, EACH F/S |
| | BRANCH TO CONNECT SEPERATELY TO MAIN |
| | VENTED LINE, MIN SIZE 3". |
| | END OF COMMENTSPAUL SCHMITZ |