| Plan Review Notes For Permit 01021024 |
| Permit Number |
01021024 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-06-18 00:00:00 | SHEET H8.4SMOKE CONTROL SEQUENCEDOES | | | NOT APPEAR TO ADDRESS THE REQUIEMENTS | | | OF SBC 414.8 FOR OTHER OCCUPIED SPACES | | | SUCH AS THE VARIOUS GALLERIES ON ALL | | | THREE FLOORS. | | | | | | WILL THE ATRIUM BEUNDER POSITIVE OR | | | NEGATIVE PRESSURE DURING SMOKE REMOVAL | | | OPERATIONS?HAS THE EFFECT ON | | | OPERATION OF THE TWO STAIR SHAFT DOORS | | | BEEN ANALYZED UNDERBOTH | | | +/- PRESSURES. | | | | | | | | | | | | PROVIDE ACCEPTANCE REPPORTS AND TEST | | | DATA FOR THE DOORS WINDOWS AND ROOF | | | COVERINGS.INCLUDE METHOD OF HURRICANE | | | MISSILEIMPACT RESISTANCE. |
|