| Date |
Text |
| 2001-03-01 00:00:00 | 1) PLEASE INDICATE PROPOSED FIRE RESCUE |
| | INGRESS AND EGRESS POINTS TO THE NEW |
| | ADDITION. |
| | 2) PLEASE LOCATE EXISTING FIRE HYDRANT |
| | LOCATIONS FOR MUSEUM. |
| | 3) PLEASE PROVIDE MORE DETAILS ON GATES |
| | LOCATED NEAR SOUTH DIXIE FOR DROP OFF |
| | LANE. |
| | 4) PROVISIONS ARE TO BE MADE FOR AT |
| | LEAST TWO HANDICAPPED PERSONS. |
| | 5) MAXIMUM TRAVEL DISTANCE NOTE ON CD1.1 |
| | IS INCORRECT. MAXIMUM TRAVEL DISTANCE |
| | IN SPRINKLERED BUILDINGS OF THIS TYPE IS |
| | 200 FEET. |
| | 6) PLEASE FURTHER CLARIFY CD1.1. EXIT |
| | SIGNS AND DOORS MUST BE SHOWN. PLAN WAS |
| | DIFFICULT TO FOLLOW. |
| | 7) PLEASE ADVISE HOW DEMOLITION WILL |
| | OCCUR WHEN THE MUSEUM IS OPEN. |
| | 8) PLEASE PROVIDE PRODUCT APPROVAL FOR |
| | ONE HOUR FIRE RATED GLAZING IN CORRIDOR |
| | 101. |
| | 9) PLEASE INDICATE HOW ILLUMINATED |
| | EXIT SIGNS WILL BE INSTALLED IN OFFICES |
| | 230 DUE TO HEADROOM ISSUES. |
| | 10) PLEASE PROVIDE MORE DETAILS ON |
| | EMERGENCY GENERATOR 227. |
| | 11) PLEASE ADVISE WHAT THE OPEN SHAFT |
| | SPACE IS FOR ON PAGE A2.2. |
| | 12) PLEASE INDICATE COMPLIANCE WITH |
| | ATRIUM REQUIREMENTS IN THE LIFE SAFETY |
| | CODE. THE DESIGN OF THE ATRIUM IS TO BE |
| | DONE BY A LICENSED ENGINEER AND THE |
| | PLANS ARE TO BE SIGNED AND SEALED. |
| | PLEASE PROVIDE TESTING REQUIREMENTS AND |
| | EQUIPMENT THAT WILL BE NEEDED TO TEST |
| | THE ATRIUM SMOKE EXHAUST SYSTEM. PLEASE |
| | INDICATE WHAT THE FIREFIGHTERS ATRIUM |
| | OVERRIDE PANEL WILL LOOK LIKE. ALSO |
| | PLEASE INDICATE THE NUMBER OF REQUIRED |
| | AIR CHANGES THAT ARE REQUIRED. |
| | 13) PLEASE PROVIDE INTERIOR FINISH |
| | CLASSIFICATION INFORMATION. |
| | 14) ELEVATORS TO COMPLY WITH ANSI A17.1. |
| | PHASE ONE AND PHASE TWO ELEVATOR RECALL |
| | WILL BE REQUIRED. |
| | 15) ALL STAIRS TO COMPLY WITH NEW STAIRS |
| | NFPA 101, THE LIFE SAFETY CODE, 1985 |
| | EDITION. |
| | 16) PLEASE INDICATE WHAT THE RAISED |
| | PLATFORM ON THE NORTH INTERIOR |
| | ELEVATION WILL BE USED FOR. |
| | 17) NATURAL GAS INSTALLATION TO COMPLY |
| | WITH NFPA 54. |
| | 18) FIRE SPRINKLER DRAWINGS NOT SIGNED |
| | AND SEALED. NO HYDRAULIC CALCULATIONS |
| | PROVIDED WITH PLANS. PLEASE PROVIDE |
| | MORE DETAILS ON PRE-ACTION SPRINKLER |
| | SYSTEM. |
| | 19) PLEASE PROVIDE MORE DETAILS FOR THE |
| | TEMPORARY RELOCATION OF THE FIRE PUMP |
| | AND FIRE MAIN. IF APPROVED BY THIS |
| | OFFICE, WHEN DOES THIS ACTIVITY OCCUR. |
| | 20) THE CHILLER ROOM IS TO BE EQUIPPED |
| | WITH APPROPRIATE SIGNAGE, ALARMS, AND |
| | HAVE SELF-CONTAINED BREATHING APPARATUS |
| | SINCE REFRIGERATOR LEAK DETECTION IS |
| | NOTED ON THE PLANS. |
| | |
| | CAPTAIN MIKE CARSILLO |
| | 659-8096,EXT.8497 |
| | 835-2910 |