| Plan Review Notes For Permit 01020979 |
| Permit Number |
01020979 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-05-01 00:00:00 | 1) ANOTHER FIRE HYDRANT WILL BE REQUIRED | | | ON 45TH STREET NEAR THE EMPLOYEE | | | ENTRANCE DRIVEWAY. | | | 2) ALL FIRE MAINS THAT ARE PLANNED FOR | | | INSTALLATION TO BE FIRE PROTECTION | | | LISTED AND COMPLY WITH NFPA 24, THE | | | STANDARD FOR FIRE SERVICE MAINS AND | | | THEIR APPURTENCES. | | | 3) PLEASE PROVIDE MORE DETAILS ON FIRE | | | PUMP HOUSE SHOWN ON SHEET 14 OF 26. | | | PLEASE INDICATE IF THE FIRE PUMP WILL | | | BE ELECTRIC OR DIESEL. WHAT SIZE FIRE | | | PUMP IS PLANNED? | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096 EXT. 8497 | | | 835-2910 |
|