Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-05-01 00:00:001) ANOTHER FIRE HYDRANT WILL BE REQUIRED
 ON 45TH STREET NEAR THE EMPLOYEE
 ENTRANCE DRIVEWAY.
 2) ALL FIRE MAINS THAT ARE PLANNED FOR
 INSTALLATION TO BE FIRE PROTECTION
 LISTED AND COMPLY WITH NFPA 24, THE
 STANDARD FOR FIRE SERVICE MAINS AND
 THEIR APPURTENCES.
 3) PLEASE PROVIDE MORE DETAILS ON FIRE
 PUMP HOUSE SHOWN ON SHEET 14 OF 26.
 PLEASE INDICATE IF THE FIRE PUMP WILL
 BE ELECTRIC OR DIESEL. WHAT SIZE FIRE
 PUMP IS PLANNED?
  