| Plan Review Notes For Permit 01020979 |
| Permit Number |
01020979 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-02-28 00:00:00 | 1) THE PLANS MAKE REFERENCE TO OTHER | | | CITIES REGARDING THE FIRE HYDRANTS, | | | MANHOLES AND OTHER APPURTENANCES. PLEASE | | | CLARIFY UTILITY ARRANGEMENTS TO THIS | | | OFFICE PRIOR TO ANY FURTHER PLAN REVIEWS | | | BEING CONDUCTED. | | | 2) IF THE BUILDING FALLS UNDER THE | | | JURISIDICTION OF THE CITY OF WEST PALM | | | BEACH, PLEASE EXPLAIN THE GUARD BOOTH | | | CANOPY ELEVATION. IF FIRE TRUCKS AND | | | PARAMEDICAL EQUIPMENT ARE EXPECTED TO | | | PASS UNDERNEATH IT, IT MUST PROVIDE AN | | | ELEVATION OF AT LEAST 13' - 6" ABOVE | | | GRADE. | | | 3) A FIRE LANE WILL BE REQUIRED FOR THE | | | BUILDING. THE REQUIRED FIRE LANE(S) | | | SHALL BE AT LEAST 20 FEET IN CLEAR WIDTH | | | AND BE PROPERLY IDENTIFIED WITH | | | APPROPRIATE SIGNAGE AND PAVEMENT | | | MARKINGS. | | | 4) IF THE BUILDING FALLS UNDER THE | | | AUSPICES OF WEST PALM BEACH, THEN THE | | | BUILDING ADDRESS IS TO COMPLY WITH | | | CITY CODE REQUIREMENTS. | | | 5) GATES WHEN INSTALLED ARE TO BE | | | ACCESSIBLE TO FIRE AND PARAMEDICAL | | | EQUIPMENT. | | | 6) FIRE HYDRANTS AND FIRE MAINS TO | | | COMPLY WITH NFPA 24, THE STANDARD FOR | | | UNDERGROUND FIRE MAINS AND THEIR | | | APPURTENANCES. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|