| Date |
Text |
| 2001-02-27 00:00:00 | FAILED: |
| | 1. PLAN NOTES AND MANHOLE COVERS REFER |
| | TO OTHER MUNICIPALITIES, PLEASE CORRECT |
| | TO CITY OF WEST PALM BEACH, SEE SHEET |
| | 15, 19, 21 AND 25. |
| | 2. PLEASE ADD NOTES STATING THAT THE |
| | CONTRACTOR TO OBTAIN ALL THE REQUIRED |
| | PERMITTING FOR LANE CLOSURE DURING THE |
| | ROADWAY CONSTRUCTION. |
| | 3. NEW SHOULDER, SWALE AREA ALONG THE |
| | 45TH STREET SHOULD BE SODDED. |
| | 4. USE DOUBLE LINE 4" WIDE TO DIMENSION |
| | THE PARKING STALL PER CITY OF WPB |
| | REQUIREMENT. |
| | 5. ALL DRIVEWAY REPAIR / REPLACEMENT |
| | SHOULD BE PER CITY OF WPB'S STANDARD AND |
| | DETAILS. |
| | 6. TRUCK WASHOUT AREA SHOULD BE PROVIDED |
| | DURING THE CONSTRUCTION. THIS WOULD BE |
| | ADDED TO THE EROSION / POLLUTION CONTROL |
| | PLAN. YOU MAY CONTACT THE CITY OF WPB |
| | FOR DETAILS. |
| | 7. IF THE GARBAGE IS TO BE PICKED UP BY |
| | THE CITY OF WPB, THEN DUMPSTER WHICH |
| | MEETS THE CITY'S REQUIREMENT SHOULD BE |
| | DETAILED.YOU MAY CONTACT THE CITY OF |
| | WPB FOR DETAILS. |
| | 8. WE RECOMMEND THAT YOU ADD A RECYCLING |
| | CENTER TO YOUR DUMPSTER ENCLOSURE. |
| | 9. PLEASE PROVIDE PERVIOUS AND |
| | IMPERVIOUS AREA COMPUTATIONS IN A 8 1/2 |
| | X 11 SHEET SIGNED AND SEALED BY THE |
| | DESIGN ENGENEER.IT WILL INCLUDE |
| | PROJECT NAME, PROPERTY CONTROL NUMBER |
| | AND ADDRESS.THIS DATA WILL BE USED TO |
| | COMPUTE THE STORM WATER CHARGES TO THE |
| | PROPERTY.THIS CAN BE DONE WITH PERMIT |
| | APPLICATION. |
| | 10. SHOW THE LOCATION AND CONNECTION |
| | FOR WATER METER AND BACKFLOW PREVENTERS. |
| | 11. SHOW THE LOCATION AND CONNECTION |
| | FOR IRRIGATION METER AND BACKFLOW |
| | PREVENTERS. |
| | 12. ALL BACKFLOW PREVENTERS SHOULD BE |
| | COMPLETELY HIDDEN FROM VIEW WITH SHRUBS |
| | PRIOR TO ACTIVATION. |
| | 13. ALL METERS SHOULD BE ACCSSIBLE. |
| | 14. SHOW THE LOCATION OF CLEAN OUT |
| | POINTS. |
| | 15. SHOW THE LOCATION OF SAMPLE PIONTS |
| | ON WATER LINES. |
| | 16. NO TREES, PLANTS, SIGN POSTS, SHALL |
| | BE PLACED WITHIN 5' OF ANY HYDRANTS, |
| | CLEAN OUT, WATER METERS, SANITARY AND |
| | STORM WATER LINES. |
| | 17. SHOW THE LOCATIONS OF WATER, SEWER, |
| | STORM WATER CONFLITS AND REFER TO THE |
| | APPROPRIATE DETAILS / PLAN PROFILES. |
| | 18. PLEASE VERIFY THAT THE SITE PLAN FOR |
| | LIFT STATION AS SHOWN ON SHEET 22 |
| | APPLIES. |
| | 19. PLEASE CONTINUE THE SERVICES TO THE |
| | END OF PROPERTY ON 45TH STREET. |
| | 20. PLEASE PROVIDE EASEMENT FROM THE |
| | LOCATION OF CONNECTIONS TO 45TH STREET. |
| | 21. CONTACT PUBLIC UTILITIES DEPARTMENT |
| | FOR LATEST DETAILS / CHART, FOR THRUST |
| | BLOCKS. |
| | 22. A R.O.W PERMIT MUST BE OBTAINED AT |
| | PUBLIC UTILITIES ENGINEERING SERVICES |
| | FOR ALL WORK WITHIN THE R.O.W. |
| | 23. CONTRACTOR SHALL MAINTAIN A FREE |
| | FLOW OF TRAFFIC DURING CONSTRUCTION. |
| | 24. CONTACT ORVILLE POLK 561- 659-8005 |
| | EXT. 2008 PRIOR TO INSTALLING BACKFLOWS |
| | AND DCDA. |
| | 25. FOR STANDARD DETAILS PLEASE CONTACT |
| | JANICE TARBILL 561-659-8088 EXT. 2303 |
| | 26. PLEASE SUBMIT SHOP DRAWING ON ALL |
| | MATERIALS USED IN R.O.W TO PUBLIC |
| | UTILITIES ENGINEERING SERVICES DIVISION: |
| | 1000 45TH STREET WEST PALM BEACH FL |
| | 33415. |
| | 27. 1-800432-4770 CALL SUNSHINE LOCATION |
| | SERVICES. 48 HOURS BEFORE DIGGING. |
| | SHOULD BE ON ALL SHEETS WHERE UTILITIES |
| | WILL BE INSTALLED IN THE R.O.W. |
| | 28. FOR CONNECTIONS AND ALL THE WORKS IN |
| | CITY'S R.O.W, PLEASE CONTACT, PUBLIC |
| | UTILITIES ENGINEERING SERVICES |
| | 1000 45TH STREET WEST PALM BEACH, FL |
| | 33415561-659-8040 EXT. 2306 |
| | IF ANY QUESTION PLEASE CONTACT |
| | 561- 659- 8096 EXT. 8492 |