Plan Review Notes
Plan Review Notes For Permit 01020951
Permit Number 01020951
Review Stop FS
Sequence Number 1
Notes
Date Text
2001-03-05 00:00:001) FIRE DEPARTMENT CONNECTION TO BE
 WITHIN 150 FEET OF A FIRE HYDRANT.
 2) ALL AREAS OF THE NEW ADDITION ARE
 TO BE FIRE SPRINKLER PROTECTED.
 3) BACKFLOW DEVICE TO BE SUPERVISED
 BY ALARM EQUIPMENT. CONTROL VALVES ALSO
 TO BE CHAINED AND LOCKED.
 4) FIRE SPRINKLER SYSTEM ADDITION TO BE
 MONITORED BY A LICENSED UL LISTED
 CENTRAL STATION.
  