| Plan Review Notes For Permit 01020942 |
| Permit Number |
01020942 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-03-09 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED | | | ON PLANS. SHOULD READ 1985 EDITION | | | INSTEAD OF 1997 EDITION. | | | 2) STORAGE ROOMS OR AREAS TO BE | | | SEPARATED FROM OTHER PARTS OF THE | | | BUILDING BY AT LEAST ONE HOUR AND ALL | | | OPENINGS SHALL BE PROTECTED BY | | | SELF-CLOSING FIRE DOORS. RE: NFPA 101, | | | THE LIFE SAFETY CODE, 1985 EDITION, | | | SECTION 27-3.2, PROTECTION FROM HAZARDS. | | | 3) PLEASE EXPLAIN RATIONALE FOR A | | | SINGLE MEANS OF EGRESS FROM THE SECOND | | | FLOOR. | | | 4) NO EMERGENCY LIGHTING SHOWN FOR THE | | | SECOND FLOOR. | | | 5) NO INTERIOR FINISH INFORMATION SHOWN | | | ON THE PLANS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|