| 2001-03-06 00:00:00 | THIS BUILDING APPEARS TO EXCEED THE |
| | 16000 FEET IN AREA ALLOTTED BY TABLE |
| | 500 FOR TYPE IV CONSTRUCTION EVEN WITH |
| | AREA INCREASES APPLIED.PLEASE PROVIDE |
| | A SURVEYSO THAT COMPLIANCE MAY BE |
| | DETERMINED. |
| | |
| | SBC F102.2.5 REQUIRES CERTAIN BUILDINGS |
| | LOCATED IN THE FIRE DISTRICT TO BE |
| | ONE HOUR PROTECTED.PLEASE REVISE AS |
| | NECESSARY |
| | |
| | ALSO SHOW THE FIRE RATED MIXED OCCUPANCY |
| | SEPARTION REQUIRED BY SBC 704.1. |
| | |
| | THE MEZZANINE SHOWN ON SHEET A4.1 DOES |
| | NOT MEET THE CRITERIA FOR A MEZZANINE |
| | CONTAINED IN SBC 503.2.3 AND IS A STORY. |
| | |
| | TWO INDEPENDENT MEANS OF EGRESS ARE |
| | REQUIRED FROM THE SECOND FLOOR.SEE |
| | SBC 1004.2.1 AND SBC 1027.1.SEE ALSO |
| | "EXIT DISCHARGE" REQUIEMENTS OF SBC |
| | 1010.1. |
| | |
| | THE EXIT STAIRS ARE REQUIED TO BE |
| | ENCLOSED BY SBC 1006.1 AND THE STORAGE |
| | AREA UNDER THE STAIRS REQUIRES ONE HOUR |
| | RATING IN ACCORDANCE WITH SBC 1006.1. |
| | |
| | SHOW THE TYPE AND QUANTITY OF MATERIALS |
| | TO BE STORED SO THAT COMPLIANCE WITH SBC |
| | 312.2 MAY BE DETERMINED. |
| | |
| | INDICATE WHERE OR PROVIDE AS NECESARY, |
| | THE FIRE RATED SEPARATION REQUIRED BY |
| | SBC 411.5.3. |
| | |
| | THE NEW GLAZING MUST COMPLY WITH THE |
| | CITY'S HURRICANE MISSILE IMPACT |
| | RESISTANCE POLICY. |
| | |
| | IMPACT FEES MUST BE PAID TO THE COUNTY |
| | FOR THE CITY, ON THE PROPOSED NEW AREA. |
| | CALL 233-5025 FOR MORE INFORMATION. |
| | |
| | SHOW HOW THE VENTILATION FOR THE NEW |
| | AREA WILL BE PROVIDED.SEE SMC 403 |
| | (MECHANICAL CODE). |