2001-08-20 00:00:00DENIED
 REFERENCE 1994 SPC
  
 1) PAGE P-2 ISLAND SINK DETAIL.
 SINK NOT VENTED PROPERLY. THIS IS NOT A
 COMBINATION WASTE AND VENT SYSTEM. WATER
 CLOSETS ARE NOT ALLOWED. 921.2.1. NOT AN
 APPROVED SYSTEM. 921.1. VENT DOWN STREAM
 REQUIRED IF IT WERE APPROVED. 921.4.2
  
 2) PAGE P3.2 LAV DETAIL. LAV TO MEET
 FACBC - 97 REQUIREMENT 4.19.2, APRON TO
 BE 29" FROM FINISHED FLOOR.
  
 REVIEW KEN STEVENS
 (561) 659-8096 EXT. 8377