| Plan Review Notes For Permit 01020941 |
| Permit Number |
01020941 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-03-24 00:00:00 | DENIED; | | | | | | 1.PAGE CS PLUMBING CODE IS THE 1994 | | | STANDARD PLUMBING CODE NOT 97. | | | | | | 2.AIR CHAMBERS TO COMPLY WITH SPC | | | 607.8.2 AND 607.8.3. | | | | | | 3.WATER HEATER TO BE READLY ACCESSIBLE. | | | CABINET SHALL HAVE A HINGED DOOR. | | | 501.7. | | | | | | 4.DRINFING FOUNTAINS SHALL COMPLY WITH | | | FACBC 4.1.3 (10) AND 4.15 FOR PEOPLE | | | WHO HAVE TROUBLE BENDING AND STOOPING. | | | | | | 5.SHOW CLEAR FLOOR SPACE FOR LAVITORY. | | | BATHROOM DOOR CANNOT SWING INTO CLEAR | | | FLOOR SPACE. SEC. 4.19.3 | | | | | | 6.FLOOR PLAN SHOWS VANITY IN BATHROOM. | | | SHEET 5.1 SHOWS WALL HUNG LAV. LAV. | | | SHALL COMPLY WITH FACBC SEC. 4.19.2. | | | | | | 7.CIVIL DRAWINGS NOT WITH PLANS SUBMITED | | | SHOW WHERE POTABLE WATER COMES FROM | | | AND WHERE RAIN WATER GOES. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8377 |
|