2001-03-24 00:00:00DENIED;
  
 1.PAGE CS PLUMBING CODE IS THE 1994
 STANDARD PLUMBING CODE NOT 97.
  
 2.AIR CHAMBERS TO COMPLY WITH SPC
 607.8.2 AND 607.8.3.
  
 3.WATER HEATER TO BE READLY ACCESSIBLE.
 CABINET SHALL HAVE A HINGED DOOR.
 501.7.
  
 4.DRINFING FOUNTAINS SHALL COMPLY WITH
 FACBC 4.1.3 (10) AND 4.15 FOR PEOPLE
 WHO HAVE TROUBLE BENDING AND STOOPING.
  
 5.SHOW CLEAR FLOOR SPACE FOR LAVITORY.
 BATHROOM DOOR CANNOT SWING INTO CLEAR
 FLOOR SPACE. SEC. 4.19.3
  
 6.FLOOR PLAN SHOWS VANITY IN BATHROOM.
 SHEET 5.1 SHOWS WALL HUNG LAV. LAV.
 SHALL COMPLY WITH FACBC SEC. 4.19.2.
  
 7.CIVIL DRAWINGS NOT WITH PLANS SUBMITED
 SHOW WHERE POTABLE WATER COMES FROM
 AND WHERE RAIN WATER GOES.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377