| 2001-05-23 00:00:00 | FAILED: | | | 1. PLEASE PROVIDE STORM WATER | | | CALCULATINS FOR OUR REVIEW IF YOU HAVE | | | NOT SUBMITTED TO JOSE DEL RIO, STORM | | | WATER ENGINEER AT 1000 45TH STREET WEST | | | PALM BEACH, FL 33407. SEE ATTACHED | | | 2. PLEASE PROVIDE CALCULATIONS FOR | | | PERVIOUS AND IMPERVIOUS AREA FOR ENTIRE | | | SITE DUE TO ALL PROPOSED CHANGES.THE | | | TOTAL AMOUNT MUST BE EQUAL TO 100 % OF | | | TOTAL SITE ACRES OR S.F.THIS DATA WILL | | | BE USED TO CALCULATE STORM WATER CHARGES | | | TO PROPERTY.PROVIDE THIS DATA ON A | | | 8 1/2 X 11 SHEET SIGNED & SEALED BY | | | DESIGN ENGINEER. PLEASE INCLUDE NAME, | | | ADDRESS AND PROPERTY CONTROL NUMBER. | | | 3. ANY NEW CONNECTION TO CITY UTILITY | | | SERVICES REQUIRES A SEPARATE PERMIT | | | THROUGH PUBLIC UTILITIES ENGINEERING | | | SERVICES DEPARTMENT 1000 45TH STREET | | | WEST PALM BEACH, FL 33407. | | | 4. POLLUTION PREVENTION PLAN MUST BE | | | INSTALLED IN THE FIELD PRIOR TO ANY | | | EARTH WORK / DEMOLITIONS WORK.PLANS | | | MUST BE KEPT ON SITE THROUGH OUT THE | | | CONSTRUCTION TIME. |
|