Plan Review Notes
Plan Review Notes For Permit 01020941
Permit Number 01020941
Review Stop B
Sequence Number 1
Notes
Date Text
2001-03-14 00:00:00PERMIT #01020941
 420 OKEECHOBEE BLVD
 SUNCOAST AUTO BUILDERS
 (727) 561-0764
  
 1)- SBC 104.2.2: ADDITIONAL INFORMATION,
 SURVEY SIGNED,SEALED AND DATED LESS THAN
 ONE YEAR OLD.F102.2.6SITE PLAN TO SHOW A
 ASSUMED PROPERTY LINE BETWEEN BUILDINGS.
 2)- SBC 1606.4.1 COUNTY AMENDMENTS:
 FOR GLAZED OPENINGS, WINDOWS & DOORS
 TESTING REPORTS FOR LARGE MISSLE IMPACT
 RESISTANCE ARE REQUIRED,EITHER SBCCI OR
 DADE COUNTY ACCEPTED,WITH THE ASSOCIATED
 TECHNICAL DRAWINGS. GLAZED OPENINGS THAT
 HAVN'T RECEIVED APPROVAL FOR LARGE MIS-
 SLE IMPACT TESTING WILL REQUIRE STORM
 SHUTTERS WITH THIS APPROVAL.
 3)- SBC 1707.4 GLAZED OPENINGS ARE RE-
 QUIRED TO HAVE TESTING FOR 1 1/2 TIMES
 THE DESIGN PRESSURE.TESTING TO BE AN
 APPROVED LABORATORY AND LISTED OR CERTI-
 FIED FOR COMPLIANCE FOR COMPLIANCE BY A
 NATIONALLY RECOGNIZED WINDOW/DOOR
 CERTIFICATION PROGRAM, SBCCI OR DADE
 COUNTY.
  
 4)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 THE CITY REQUIRES INFORMATION ON THE
 BUCK ATTACHMENT TO THE CONCRETE COLUMNS
 AND MASONARY BLOCK UNITS.
  
 5)- FIRE DISTRICT! F102.4 ROOF COVERINGS
 SHALLCONFORM TO THE REQUIREMENTS OF
 CLASS A OR B ROOF COVERINGS.
  
 6)- SBC708.5 ROOF INSULATION RATING:
 FLAME SPREAD RATING & SMOKE DEVELOPMENT.
  
 7)- SBC 1606.3.2: INSULATION FASTENING
 SCHEDULE FOR THE ROOF.
  
 8)- SBC 606 TYPE IV CONSTRUCTION: NON-
 COMBUSTIBLE MATERIALS ARE TO BE USED IN
 THE PARAPET WALL, NO 1/2 " PLYWOOD
 ALLOWED. SBC 707-(3) DOES ALLOW FIRE RE-
 TARDANT TREATED WOOD.
  
 9)- SBC 1517 ROOF OVERFLOW SCUPPERS ARE
 TO BE NO LESS THAN 2" ABOVE THE ROF AND
 NOT MORE THAN 4" ABOVE THE ROOF SEE PLAN
 ARCH.4.2.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412