| 2001-03-14 00:00:00 | PERMIT #01020941 |
| | 420 OKEECHOBEE BLVD |
| | SUNCOAST AUTO BUILDERS |
| | (727) 561-0764 |
| | |
| | 1)- SBC 104.2.2: ADDITIONAL INFORMATION, |
| | SURVEY SIGNED,SEALED AND DATED LESS THAN |
| | ONE YEAR OLD.F102.2.6SITE PLAN TO SHOW A |
| | ASSUMED PROPERTY LINE BETWEEN BUILDINGS. |
| | 2)- SBC 1606.4.1 COUNTY AMENDMENTS: |
| | FOR GLAZED OPENINGS, WINDOWS & DOORS |
| | TESTING REPORTS FOR LARGE MISSLE IMPACT |
| | RESISTANCE ARE REQUIRED,EITHER SBCCI OR |
| | DADE COUNTY ACCEPTED,WITH THE ASSOCIATED |
| | TECHNICAL DRAWINGS. GLAZED OPENINGS THAT |
| | HAVN'T RECEIVED APPROVAL FOR LARGE MIS- |
| | SLE IMPACT TESTING WILL REQUIRE STORM |
| | SHUTTERS WITH THIS APPROVAL. |
| | 3)- SBC 1707.4 GLAZED OPENINGS ARE RE- |
| | QUIRED TO HAVE TESTING FOR 1 1/2 TIMES |
| | THE DESIGN PRESSURE.TESTING TO BE AN |
| | APPROVED LABORATORY AND LISTED OR CERTI- |
| | FIED FOR COMPLIANCE FOR COMPLIANCE BY A |
| | NATIONALLY RECOGNIZED WINDOW/DOOR |
| | CERTIFICATION PROGRAM, SBCCI OR DADE |
| | COUNTY. |
| | |
| | 4)- SBC 1606.2.6.2 COMPONENTS & CLADDING |
| | THE CITY REQUIRES INFORMATION ON THE |
| | BUCK ATTACHMENT TO THE CONCRETE COLUMNS |
| | AND MASONARY BLOCK UNITS. |
| | |
| | 5)- FIRE DISTRICT! F102.4 ROOF COVERINGS |
| | SHALLCONFORM TO THE REQUIREMENTS OF |
| | CLASS A OR B ROOF COVERINGS. |
| | |
| | 6)- SBC708.5 ROOF INSULATION RATING: |
| | FLAME SPREAD RATING & SMOKE DEVELOPMENT. |
| | |
| | 7)- SBC 1606.3.2: INSULATION FASTENING |
| | SCHEDULE FOR THE ROOF. |
| | |
| | 8)- SBC 606 TYPE IV CONSTRUCTION: NON- |
| | COMBUSTIBLE MATERIALS ARE TO BE USED IN |
| | THE PARAPET WALL, NO 1/2 " PLYWOOD |
| | ALLOWED. SBC 707-(3) DOES ALLOW FIRE RE- |
| | TARDANT TREATED WOOD. |
| | |
| | 9)- SBC 1517 ROOF OVERFLOW SCUPPERS ARE |
| | TO BE NO LESS THAN 2" ABOVE THE ROF AND |
| | NOT MORE THAN 4" ABOVE THE ROOF SEE PLAN |
| | ARCH.4.2. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 EX 8412 |