| Plan Review Notes For Permit 01020814 |
| Permit Number |
01020814 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-05-09 00:00:00 | ********************PROVISO************* | | | | | | MECHANICAL PERMIT #01031167. | | | | | | | | | ACCESS DOOR TO SUSPENDED AHU SHALL HAVE | | | ADIQUATE SPACE AS TO REMOVE THE LARGEST | | | PIECE OF EQUIPMENT BUT NOT LESS THAN 22" | | | X 36".(1997 SMC 304.4.1) | | | | | | CONDENSER UNIT STAND SHALL BE A MINIMUM | | | OF 18" FROM ROOF SURFACE TO BOTTOM OF | | | SUPPORT RAIL. (AMENDED 1997 SMC 304.4.2) |
|