Plan Review Notes
Plan Review Notes For Permit 01020752
Permit Number 01020752
Review Stop R
Sequence Number 1
Notes
Date Text
2001-03-17 00:00:00CHECKLIST:
 1-PAY IMPACT FEES.
 2-NEED NOTICE OF COMMENCEMENT. (NOC)
 3-SPECIFY DRAFSTOPPING MATERIAL AND
 LOCATION AT 2ND FLOOR FRAMING PLAN.
 SEC. 2305.2 SBC 1997.
 4-PROVIDE CURRENT SBCCI OR DADE COUNTY
 PRODUCT APPORVAL FOR:
 -OUTSWING ENTRY DOORS W/ TRANSOM ABOVE
 ASSEMBLY AS SHOWN ON EXTERIOR ELEVAT'N
 -FIXED WINDOWS W/ SIZE SHOWN ON PLANS.
 -GARAGE DOORS THAT MEET THE DESIGN
 PRESSURES CALCULATED BY THE ARCHITECT.
 -ROUND WINDOWS AS SHOWN ON PLANS.
 -BBQ UL LISTING AND SPECIFICATIONS.
 5-SIZE OF EGRESS WINDOW AT BEDROOM #3
 DOESN'T MEET THE MINIMUM SIZE AS
 REQUIRED BY SEC 1005.4.4 SBC 1997.
 6-SPECIFY SAFETY GLASS WHERE REQUIRED.
 2405.2 SBC/97. SEE PLANS FOR COMMENTS.
 7-PROVIDE COMPLETE STAIR DETAIL/SECTION
 THAT APPLIES TO THIS HOUSE. SEE PLANS.
 SEC. 104.2.2 CITY AMENDMENTS TO
 SBC/978-REVISE INSTALLATION
 SPECIFICATIONS FOR
 CEILING AT EXTERIOR PORCHES. SEE
 ASTM C 1063 AND PROVIDE COMPLETE
 SPECS9-SPECIFY HOW IS ROOF CROSS
 VENTILATION
 ACHIEVED IF ATTIC VENTS ARE CLOSED AT
 ZERO LOT LINE WALL. SEC 2309.6 SBC/97.
 10-FOOTINGS TO BE 12" MIN. BELOW GRADE.
 SEC 1804.1.3 SBC/97. REVISE SECTIONS.
 11-SOIL TEST REPORT MUST HAVE ENGINEER'S
 ORIGINAL SIGNATURE AS REQUIRED BY
 CHAPTER 471 OF FLORIDA STATUTES.
 12-REVISE ENERGY CALCULATIONS. THERE ARE
 4 BEDROOMS, CONSIDERING THE DEN ROOM.
 13-STORM PANELS: PROVIDE KEY PLAN AND
 COMPLETE INSTALLATION SCHEDULE (SEE
 ATTACHED CITY SAMPLE).
 -CLEARLY INDICATE ON DRAWINGS THE
 MOUNTING SYSTEMS TO BE USED AND ANCHOR
 TYPE AND SPACING TO BE USED ACCORDING
 TO THE MEAN ROOF HEIGHT, THE DESIGN
 PRESSURES, PANEL SPAN, EDGE DISTANCE,
 CONNECTION TYPE AND STRUCTURE TO BE
 ATTACHED TO (CONCRETE BLOCK OR WOOD).
 14-REVISE TRUSS DRAWINGS:
 -THERE IS ONLY ONE MEAN ROOF HEIGHT FOR
 ENTIRE BUILDING. TABLE 1606.2A SBC/97.
 SEE ARCHITECT'S PLANS.
 -EDITION OF THE STANDARD BUILDING CODE
 1997 IS WRITTEN BY HAND. THIS IS NOT
 ACCEPTABLE. IT SHOULD BE PART OF THE
 COMPUTER PROGRAM.
 -UPDATE ALL GENERAL TRUSS DRAWINGS AND
 ENGINEER TO DATE THEM W/ THE DATE HE
 SEALED AND SIGNED THEM AS REQUIRED BY
 CHAPTER 471 OF FLORIDA STATUTES.
 -ALL TRUSS DRAWINGS SHALL BE REVIEWED
 BY THE ARCHITECT PRIOR TO SUBMITTAL.
 -TRUSS LAYOUT IS MISSING 2ND FL. ROOF.
 -TRUSS ENGINEER TO PROVIDE ALL HIS
 INFORMATION AS REQUIRED BY CHAPTER
 471 OF FLORIDA STATUTES WHEN SUBMITT'G
 DOCUMENTS FOR PUBLIC RECORDS.
 15-SEE PLANS FOR ADDITIONAL COMMENTS.
 -SEE COMMENTS BY THE OTHER TRADES.
  
  
  
 * IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ, BUILDING PLAN REVIEWER,
 AT 659-8096 EXT. 8232.