| Plan Review Notes For Permit 01020752 |
| Permit Number |
01020752 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-02-28 00:00:00 | DENIED; | | | | | | 1.A/H #2 CFM'S ADD UP TO 2075 3 1/2 NOT | | | CAPABLE TO MOVE THAT MUCH AIR. | | | | | | 2.FLOOR PLAN NOT COMPLETE ROOMS MISSING | | | AND NOT NAMED. VERY HARD TO FOLLOW. | | | | | | 3.SHOW SIZE AND LOCATION OF EX-FANS, | | | VENT SIZE AND TERMINATION POINT. | | | | | | 4.FREON LINES ARE RUN HOW? | | | | | | A/C PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8377 |
|