| Plan Review Notes For Permit 01020747 |
| Permit Number |
01020747 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-04-09 00:00:00 | DENIED; | | | | | | 1.PLAN REVIEW NOTE 2 FROM 2/20/01, SHT | | | A-201 SHOW 5'TURNING RADIUS, NOT | | | ADDRESSED ON REVISED PLANS.SEE SEC. | | | FACBC 4.2.3. | | | | | | 2.NOTE 4 FROM 2/20/01 WATER HEATER TO BE | | | READLY ACCESSIBLE.SEC 501.7. INSTALL | | | HEATER ON FLOOR OR SHOW A DETAIL WITH | | | A FIXED SHIPS LADDER . | | | | | | 3.DISHWASHER SHALL DISCHARGE INDIRECTLY | | | INTO THE DRAINAGE SYSTEM. 94 SPC 409. | | | 1.2. FLOOR SINKS ARE PROPERLY TRAPPED | | | AND VENTED FIXTURES. | | | | | | 4.THREE COMPARTMENT SINKS WHEN USED FOR | | | FOOD PREP. SHALL DISCHARGE INDIRECTLY | | | INTO A FLOOR SINK. SEC. 804.1 | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8096 |
|