2001-03-04 00:00:00PLUMBING PLAN REVIEWDENIED
 REFERENCESSTD PLBG CODE-94 FACBC 97
 (1) SHT A-201 CONTACT DEPT.OF BUSINESS
 REGULATION,HOTEL & RESTAURANT DIVISION.
 PRIOR TO PLBG PLAN REVIEW, FOR THEIR
 COMMENTS & REVIEW.954 958-5520.
 (2) SHT A-201 REST RM.#1,2, SHOW 5'
 TURNING RADIUS,NOT CUTTING INTO WATER
 CLOSET CLEAR FLR SPACE. SEC 4.16.2
 (3) SHT A-201 DRINKING FOUNTAIN , MAKE
 PROVISION FOR PEOPLE WHO HAVE TROUBLE
 BENDING SEC 4.1.3 (10) (A) CUP DISPENSER
 (4)SHT P-2 WATER HEATER TO BE READLY
 ACCESSIBLE,SEC501.7 SHOW A DETAIL OF A
 WORKING PLAT FORM WITH FIXED SHIPS
 LADDER IN PLACE.
 (5) SHT P-3 ALL INDIRECT WASTE TO FLOOR
 SINKS SEC 802, NO HUB DRAINS.
 (6) SHT P-3 AIR CHAMBERS, COMPLY WITH
 SEC 607.8.3 ACCESSIBLE & RE-CHARGE-ABLE.
 (7) SHT P-3 PLUMBING NOTE #5 DWV IN THIS
 BUILDING HAS BEEN SCH 40 PVC PIPE.
 END OF COMMENTS,PAUL SCHMITZ,QUESTIONS
 561-659-8096 X 8233