Plan Review Notes
Plan Review Notes For Permit 01020747
Permit Number 01020747
Review Stop M
Sequence Number 1
Notes
Date Text
2001-03-09 00:00:00*******************DENIED***************
  
 NEED AIR BALANCE SCHEDULE AND
 INFORMATION ON AIR HANDLER UNITS OR FAN
 COILS BOTH ARE MENTIONED.
  
 INDICATE WHERE OUTSIDE AIR IS SUPPLIED
 TO FN01 FH4ANF003, AN ACCESS PANEL IS
 INDICATED ON THE DRAWING M1 IS THIS
 ALSO THE RETURN..PLEASE CLARIFY.
  
 NOTE:AS PER 1997 SMC 506.1 - 10'
 MINIMUM BETWEEN EXHAUST AND FRESH AIR
 INTAKE.UNLESS THE EXHAUST IS 24" ABOVE
 FRESH AIR INTAKE - 1997 SMC 405.
  
 NO COMBUSTIBLES ABOVE CEILING IN RETURN
 AIR PLENUM - 1997 SMC 609.1.1.