| Plan Review Notes For Permit 01020747 |
| Permit Number |
01020747 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-03-09 00:00:00 | *******************DENIED*************** | | | | | | NEED AIR BALANCE SCHEDULE AND | | | INFORMATION ON AIR HANDLER UNITS OR FAN | | | COILS BOTH ARE MENTIONED. | | | | | | INDICATE WHERE OUTSIDE AIR IS SUPPLIED | | | TO FN01 FH4ANF003, AN ACCESS PANEL IS | | | INDICATED ON THE DRAWING M1 IS THIS | | | ALSO THE RETURN..PLEASE CLARIFY. | | | | | | NOTE:AS PER 1997 SMC 506.1 - 10' | | | MINIMUM BETWEEN EXHAUST AND FRESH AIR | | | INTAKE.UNLESS THE EXHAUST IS 24" ABOVE | | | FRESH AIR INTAKE - 1997 SMC 405. | | | | | | NO COMBUSTIBLES ABOVE CEILING IN RETURN | | | AIR PLENUM - 1997 SMC 609.1.1. |
|