2001-02-21 00:00:001) NO FIRE SPRINKLER DRAWINGS INCLUDED
 WITH PLANS. PLEASE PROVIDE FIRE
 SPRINKLER DRAWINGS.
 2) PLEASE PROVIDE SEPARATE PLANS AND
 PERMITS FOR FIRE ALARM EQUIPMENT SHOWN
 ON DRAWINGS. PLEASE BE ADVISED THAT
 MANUAL PULL STATIONS ARE NOT REQUIRED
 AND CAN BE ELIMINATED. DUCT SMOKE
 DETECTORS WHEN ACTIVATED ARE TO CAUSE
 THE AIR HANDLING EQUIPMENT TO SHUT DOWN
 AND ACTIVATE THE FIRE ALARM SYSTEM.
 3) THE OCCUPANT LOAD FOR THE OUTSIDE
 CAFE WILL BE DETERMINED BY THIS OFFICE.
 4) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR THE
 WALLS AND CEILING OF THE STORE.
 5) THIS OFFICE HAS CONCERNS OVER THE
 SMOKE DEVELOPMENT INFORMATION PRESENTED
 IN THE TEST DATA PROVIDED BY UTC, INC.
  