| Plan Review Notes For Permit 01020747 |
| Permit Number |
01020747 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-02-21 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS INCLUDED | | | WITH PLANS. PLEASE PROVIDE FIRE | | | SPRINKLER DRAWINGS. | | | 2) PLEASE PROVIDE SEPARATE PLANS AND | | | PERMITS FOR FIRE ALARM EQUIPMENT SHOWN | | | ON DRAWINGS. PLEASE BE ADVISED THAT | | | MANUAL PULL STATIONS ARE NOT REQUIRED | | | AND CAN BE ELIMINATED. DUCT SMOKE | | | DETECTORS WHEN ACTIVATED ARE TO CAUSE | | | THE AIR HANDLING EQUIPMENT TO SHUT DOWN | | | AND ACTIVATE THE FIRE ALARM SYSTEM. | | | 3) THE OCCUPANT LOAD FOR THE OUTSIDE | | | CAFE WILL BE DETERMINED BY THIS OFFICE. | | | 4) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR THE | | | WALLS AND CEILING OF THE STORE. | | | 5) THIS OFFICE HAS CONCERNS OVER THE | | | SMOKE DEVELOPMENT INFORMATION PRESENTED | | | IN THE TEST DATA PROVIDED BY UTC, INC. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|