| Notes |
| Date |
Text |
| 2001-03-01 00:00:00 | ****************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE THE REQ`MENTS FOR | | | TAPPED CONDUCTORS IN 240-21-C,1,2,3. | | | YOU ARE ALSO SHOWING TAPPING CONDUCTORS | | | THAT ARE ALREADY CONSIDERED TAPPED CONDU | | | CTORS? THERE MUST BE SEPARATE RUNS FOR | | | EACH ONE TO EACH PANEL. | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 3)NOTE: PLEASE SHOW LOAD CALCUALTIONS | | | NONE SHOWN. PLEASE NOTE ALL CONTINUOUS | | | LOADS ARE TO FIGURED AT 125%. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|