| Plan Review Notes For Permit 01020724 |
| Permit Number |
01020724 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-03-14 00:00:00 | 1) FIRE SUPPRESSION SYSTEM WILL REQUIRE | | | SEPARATE PLAN AND PERMIT PRIOR TO | | | INSTALLATION. | | | 2) A MINIMUM OF THREE FEET SHALL BE | | | PROVIDED AROUND THE SPRAY BOOTH. NO | | | COMBUSTIBLE STORAGE ALLOWED IN THIS | | | AREA. | | | 3) SINCE NO PAPERWORK WAS PROVIDED WITH | | | PLANS, A LABEL IS TO BE VISIBLE DURING | | | INSPECTION OF IT. | | | 4) LIGHT FIXTURES TO COMPLY WITH NFPA 33 | | | REQUIREMENTS. | | | 5) INTAKE FILTERS TO COMPLY WITH UL 900. | | | 6) SPRAY BOOTH TO BE BONDED AND | | | GROUNDED | | | 7) SEPARATE PERMIT REQUIRED FOR THE | | | ELECTRICAL EQUIPMENT INSTALLATION. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|