Plan Review Notes
Plan Review Notes For Permit 01020724
Permit Number 01020724
Review Stop M
Sequence Number 1
Notes
Date Text
2001-03-07 00:00:00******************DENIED****************
  
 PROVIDE INFORMATION ON WHAT TYPE OF
 SPRAY BOOTH AND LOCATION INSIDE THE
 BUILDING
  
 SHOW COMPLIANCE WITH CHAPTER 5 OF NFPA
 33, PERFORMACE REQUIREMENTS, MAKE UP
 AIR (WHERE IS IT COMING FROM AND HOW
 MANY CFM IS THE EXHAUST FAN - NFPA
 33-12, 5-3) WHERE IS THE EXHAUST IS
 RELATION TO MAKE UP AIR.
  
 PROVIDE INFORMATION ON DISTRIBUTION
 SYSTEM USED IN PAINT SPRAY BOOTH,
 HOSES, PIPING SYSTEM, SHUT OFF VALVES
 ETC.INDICATE WHERE A PUMP IS USED TO
 SUPPLY LIQUID FOR THE SPRAY APPLICAITON
 PROCESS. (NFPA 33-14, 6-4.1 THRU 6-4.6)
  
 SHOW LOCATION OF ELECTRIC DEVICES IN
 SPRAY AREA, ALSO LIGHTING DETAIL ARE
 THE LIGHTS FOR INSIDE SPRAY BOOTH OR
 OUTSIDE.
  
 INDICATE WHERE THE BOOTH GROUNDED.