2001-02-20 00:00:001) WHAT IS THE SPRAY BOOTH GOING TO BE
 USED FOR.
 2) WHAT FIRE PROTECTION IS PLANNED FOR
 THE BOOTH.
 3) WHERE CAN MORE DETAILS BE LOCATED FOR
 THE PREFABRICATED BOOTH.
 4) HOW IS THE SPRAY BOOTH GOING TO BE
 GROUNDED.
 5) WHERE CAN THE CFM AMOUNT FOR THE FAN
 BE LOCATED.
 6) THE METAL DUCT MUST EXTEND A MINIMUM
 OF SIX FEET FROM THE ROOF.
 7) HOW IS THE DUCT BEING SUPPORTED
 8) HOW DOES MAKE-UP AIR ENTER THE SPRAY
 BOOTH.
  
 PLEASE SHOW COMPLETE COMPLIANCE WITH
 NFPA 33 FOR THE BOOTH AND EXHAUST DUCT.
  