| Plan Review Notes For Permit 01020724 |
| Permit Number |
01020724 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-03-15 00:00:00 | PLANS CALL FOR 20 AMP FAN AND AN | | | ADDITIONAL SET CALL FOR A 40 AMP FAN? | | | WHICH ONE ARE YOU GOING TO USE? | | | SUBMIT LOAD CALCULATION FOR THE SPACE | | | SHOWING THAT THE SERVICE IS OF | | | SUFFICIENT SIZE!!! | | | PLEASE OUTLINE ON THE PLANS THE CLASS | | | LOCATION AND WHAT CLASS IS BEING USED! |
|