| Plan Review Notes For Permit 01020706 |
| Permit Number |
01020706 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-02-23 00:00:00 | 1) PARTIAL SITE PLAN DOES NOT IDENTIFY | | | EXISTING FIRE HYDRANT LOCATIONS. | | | 2) PLEASE PROVIDE SEATING DIAGRAM. | | | 3) PLEASE INDICATE IF FIRE SPRINKLERS | | | ARE PLANNED FOR THE LUNCHROOM. | | | 4) EXITS FROM THE LUNCHROOM ARE NOT | | | PROPERLY SEPARATED FROM ONE ANOTHER. | | | 5) PROVISIONS ARE TO BE MADE FOR AT | | | LEAST TWO HANDICAPPED PERSONS. | | | 6) PLEASE PROVIDE INTERIOR FINISH | | | INFORMATION FOR THE WALLS AND CEILINGS. | | | 7) ANY CHANGES IN ELEVATIONS LESS THAN | | | 21 INCHES SHALL BE BY RAMPS. | | | | | | CAPATIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|