| Plan Review Notes For Permit 01020706 |
| Permit Number |
01020706 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-03-01 00:00:00 | *************** UNSAT **************** | | | | | | 1NOTE: PLEASE SUBMIT PLANS SHOWING ALL | | | BRANCH CIRCUIT #`S. ALL CIRCUIT ARE TO C | | | ORRELATE WITH SUBMITTED PANEL SCHEDULES. | | | | | | 2)NOTE: PLEASE SUBMIT AND SHOW LOAD | | | CALCULATIONS PER 220. PLEASE NOTE THAT | | | ALL CONTINUOUS LOADS ARE TO BE SHOWN AT | | | 125%. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|