| Notes |
| Date |
Text |
| 2001-02-27 00:00:00 | 1)SHEET S3 SECTIONS 1/S3 AND AND 3/S3 | | | HAVE CONFLICTING INFORMATION AS TO THE | | | PRECAST SIZES.PLEASE CLARIFY.SEE | | | SBC 104.2. | | | | | | 2) HOW WILL THE ANCHOR BOLTS SHOWN ON S3 | | | TYPICAL COLUMN FOOTING BE PLACED IN | | | THEEXISTING SLAB? | | | | | | 3)CLEARLY NOTE THE CONCURRENT | | | EXTENSION OF THE FIRE SPRINKLER SYSTEM. | | | SEE SBC 903.2. |
|