| Plan Review Notes For Permit 01020616 |
| Permit Number |
01020616 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-04-19 00:00:00 | DENIED; | | | | | | NOTES ARE THE SAME AS LAST REVIEW | | | | | | 1.CONTACT RODNEY COMPO AT 837-4074 FOR | | | GREASE TRAP WAVER AND LOCATION FOR | | | SAMPLE POINT. | | | | | | 2.WATER HEATER; READ DEFINITION FOR | | | READLY ACCESSIBLE. CHAPTER 2 OF THE 94 | | | SPC PROVIDE FIXED LADDER. 501.7 | | | | | | 3.CONDENSATE FROM COOLERS SHALL | | | TERMINATE TO A FLOOR SINK NOT A FLOOR | | | DRAIN. | | | | | | 4.PLEASE ADD A NOTE; IF AIR CHAMBERS ARE | | | USED THEY WILL COMPLY WITH 607.8.2 AND | | | 607.8.3. | | | | | | PLUMBINGPLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 |
|