| Plan Review Notes For Permit 01020616 |
| Permit Number |
01020616 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-04-11 00:00:00 | ******************PROVISIO************** | | | | | | AUXILIARY DRAIN PAN SHALL HAVE OVERFLOW | | | PROTECTION BY MEANS OF A FLOAT SWITCH | | | OR SEPARATE DRAIN LINE AS PER 1997 SMC | | | 304.8.6.1. | | | | | | PLEASE PROVIDE DETAIL OF REFRIGERANT | | | LINES GOING FROM CONDENSER TO AHU. | | | PLEASE ADDRESS THE ABOVE ITEMS WHEN THE | | | MECHANICAL PERMIT IS APPLIED FOR. | | | | | | ADDITIONAL MECHANICAL PERMIT REQUIRED | | | FOR WALKIN COOLER.PLEASE SUBMIT PLANS | | | WITH PERMIT APPLICATION. |
|