Plan Review Notes
Plan Review Notes For Permit 01020616
Permit Number 01020616
Review Stop M
Sequence Number 2
Notes
Date Text
2001-04-11 00:00:00******************PROVISIO**************
  
 AUXILIARY DRAIN PAN SHALL HAVE OVERFLOW
 PROTECTION BY MEANS OF A FLOAT SWITCH
 OR SEPARATE DRAIN LINE AS PER 1997 SMC
 304.8.6.1.
  
 PLEASE PROVIDE DETAIL OF REFRIGERANT
 LINES GOING FROM CONDENSER TO AHU.
 PLEASE ADDRESS THE ABOVE ITEMS WHEN THE
 MECHANICAL PERMIT IS APPLIED FOR.
  
 ADDITIONAL MECHANICAL PERMIT REQUIRED
 FOR WALKIN COOLER.PLEASE SUBMIT PLANS
 WITH PERMIT APPLICATION.