2001-03-04 00:00:00PLUMBING PLAN REVIEWDENIED
 (1) LETTER FRON CHARLOTTE RUSSELL RE:
 GREASE TRAP, CONTACT,RODNEY COMPO
 561-835-7423 W P BCH REGIONAL SEWER
 TREATMENT PLANT FOR GREASE TRAP WEAVER,
 WITH LOCATION OF SAMPLE POINT.
 (2) SHT P-1 WATER HEATER TO BE READLY
 ACCESSIBLE SPC 94 SEC 501.7 PROVIDE A
 DETAIL OF A WORKING PLATFORM WITH A
 SHIPS LADDER FIXED IN PLACE.
 (3) SHT P-1 ITEMS 34,35 ALL INDIRECT
 WASTE TO FLOOR SINKS SEC 802.
 (4) SHT P-1 AIR CHAMBERS, COMPLY WITH
 SEC.607.8.3,ACCESSIBLE & RE-CHARGE-ABLE.
 END OF COMMENTS PAUL SCHMITZ