| Plan Review Notes For Permit 01020604 |
| Permit Number |
01020604 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-02-20 00:00:00 | PROVISO: | | | | | | HEAT PUMPS REQUIRE A DRAIN PAN WITH | | | OVERFLOW PROTECTION SUCH AS FLOAT | | | SWITCH OR SECONDARY DRAIN LINE AS PER | | | 1997 SMC 304.8.6.1. | | | | | | REFERENCE DWG. M0.1, NOTE 12 -AS PER | | | NFPA 90A 4-4.4.3 (A), FAN SHUT DOWN | | | SHALL HAVE NOTIFICATION TO HORN/STROBE | | | IN NORMALLY OCCUPIED AREAS. | | | | | | NOTES ALSO ON PERMIT 01020602. |
|